77
Lutron® integration protocol
Energi Savr NodeTM QS for DALI® (continued)
OUTPUT Commands
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 Level = 0 –100 or 0.00 –100.00
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
(QSStandalone fade: maximum 90 seconds)
Delay
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
(QSStandalone delay: maximum 4 hours)
Start Raising 2 None
Start Lowering 3 None
Stop Raising / Lowering
4 None
NOTES
1. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
2. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds a value of 1.25 seconds will be used.
Example OUTPUT Commands
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set dimmer to 75% with a 1 min 30 sec fade. #OUTPUT,1,1,75,01:30<CR><LF>
Start Raising zone level. #OUTPUT,1,2<CR><LF>
Stop Raising / Lowering zone level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1. The system will report the target level of a dimmer while it is fading from one level to another.
The actual level is not transmitted while dimming between levels.
Example: If the “Over Sink” (Integration ID -1) dimmer is at 20% and is then commanded to go to 100% by sending
#OUTPUT,1,1,100 the response from the system will be ~OUTPUT,1,1,100.00
®
V
D E
Test
Power
Hi Temp
Ethernet
DALI 1 DALI 2
IR
Photo
Com
20 V
20 V
Com
MUX
MUX
24 V
COM
Occ
IR
Photo
Occ
Energi Savr Node
TM
QS
QSNE-2DAL-D
230 V~ 50/60 Hz 100 mA
www.lutron.com
+44.(0)20.7680.4481
L N
1 1 2 2
3
3 4 4
QS
8 mm
0,5 N∙m
N1771
Z096
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 1, Action Number, Parameters