Lutron® integration protocol
DEVICE Command-specific fields
Component Numbers:
Refer to device specific tables for lists of Component Numbers.
Action Numbers and Parameters:
Action Action Number Parameters
Enable 1 None
1
Disable 2 None
1
Press / Close / Occupied 3 None
Release / Open / Unoccupied 4 None
Hold
2
5 None
Multi-tap
2
6 None
Set or Get Current Scene
1,2
7 Scene
Set (#) or Get (?) LED State 9 0 = Off
1 = On
2 = Normal Flash
2
3 = Rapid Flash
2
Set or Get Light Level
3,4
14 0–100 or 0.00 –100.00
3
SS.ss, SS, MM:SS, or HH:MM:SS
3
SS.ss, SS, MM:SS, or HH:MM:SS
3
NOTES
1. Quantum® 2.7 and higher.
2. Not supported in RadioRA® 2.
3. Not supported by Quantum®.
4. Not supported by Clear Connect® Gateway.
DEVICE Command Formats
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
Continued on next page…
Integrator’s Reference (continued)
DEVICE: Command Summary
Device integration commands allow the user to access components of the system such as a
physical device. The user can activate programming via button presses, releases, etc., as well as
monitor those same events as they occur in real time in the system.