Lutron® integration protocol
Integrator’s Reference (continued)
GROUP
1
: Command Summary
The GROUP command is used to report the status of a group of occupancy sensors.
GROUP Command-specific fields
Action Numbers:
Action Action Number
Get (?) Occupancy Group State
3
GROUP Command Format
Use “GROUP Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
?GROUP, 6, Action Number
Example GROUP Messages
Operation Command String
Query: ?GROUP, Integration ID, Action Number
What is Occ GROUP 1’s status? ?GROUP,1,3<CR><LF>
Response: ~ GROUP, Integration ID, Action Number, Parameters
Occ group 1 is occupied ~GROUP,1,3,3<CR><LF>
Occ group 1 is unknown ~GROUP,1,3,255<CR><LF>
Occupancy States:
Description Value
Occupied 3
Unoccupied 4
Unknown 255