Lutron® integration protocol
DEVICE Command-specific fields (continued)
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Lock
1,2,3
15 0 = Off
1 = On
Set or Get Scene Lock
1,2,3
16 0 = Off
1 = On
Set or Get Sequence State
1,2,3
17 0 = Off
1 = Scenes 1– 4
2 = Scenes 5 –16
Start Raising
3,4,5
18 None
Start Lowering
3,4,5
19 None
Stop Raising / Lowering
3,4,5
20 None
Get battery status 22 1 = Normal, 2 = Low
Set a custom lift and tilt level of venetian blinds
programmed to the phantom button
4,6
23 Lift level %
Tilt level %
Set a custom lift level only of venetian blinds
programmed to the phantom button
4,6
24 Lift level %
Set a custom tilt level only of venetian blinds
programmed to the phantom button
4,6
25 Tilt level %
Hold / Release
2
32 None
GRAFIK Eye® QS Timeclock state 34 0 = Disabled
1 = Enabled
Query CCI state 35 None
NOTES
1. Not supported in HomeWorks® QS.
2. Not supported in RadioRA® 2.
3. Not supported by Quantum®.
4. Use OUTPUT command with equivalent action number in RadioRA® 2.
5. Use OUTPUT command with equivalent action number in HomeWorks® QS.
6. Use SHADEGRP command with equivalent action number in HomeWorks® QS.
Integrator’s Reference (continued)
DEVICE: Command Summary (continued)