AMX NXB-CCG-K Informations techniques Page 22

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 144
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 21
22
Lutron® integration protocol
Connection Information
Provides an RS232 and Ethernet connection to communicate with external equipment.
Communication is through either RS232 or Ethernet, but not both simultaneously.
RS232
The RS232 connection has the following communication settings:
Baud Rate 9600/19200/38400/115200 (set via dipswitch on unit)
8 data bits
No parity bit
1 stop bit
No flow control
Ethernet
Configuring the control interface to communicate over a network takes not only knowledge
of the QS system, but of networking as well. Installers with limited networking knowledge are
advised to contact a networking professional before attempting to connect a QSE-CI-NWK-E
through a network. The information below will help an installer communicate the QSE-CI-NWK-E
configurations to a network professional.
The installer will make any necessary changes to the control interface using the Lutron® DeviceIP or
PC software tool and the network professional can make any necessary changes to the networking
equipment.
Single Ethernet Port
IEEE® 802.3 Auto-Sensing 10BaseT / 100BaseTX
Supports MDI/MDIX auto-crossover (no crossover cable needed).
Female 8P8C “Computer RJ-45” socket
Green “Connect” LED, Amber “Activity” LED
Use Cat 5 cabling or better
TCP / IP Settings
IP Address: <static default = 192.168.250.1>
Subnet Mask: <static default = 255.255.255.0>
Gateway: <static default = 0.0.0.0>
Protocols Used for Integration
TELNET
Telnet Server
Used by third party equipment (i.e. touch screen)
Limited to transferring ASCII characters
Telnet Port number is 23
Login #1: nwk
Login #2: nwk2
QS Standalone (continued)
Integration Access Points (continued)
Vue de la page 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 143 144

Commentaires sur ces manuels

Pas de commentaire