Appendix B Accessories|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 B-33
575V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance 5% impedance
0.75 1 2 3 20 32
1.5 2 4 6 9 12
2.2 3 4 6 9 12
3.7 5 8 12 5 7.5
5.5 7.5 8 12 3 5
7.5 10 12 18 2.5 4.2
11 15 18 27 1.5 2.5
15 20 25 37.5 1.2 1.8
18.5 25 25 37.5 1.2 1.8
22 30 35 52.5 0.8 1.2
30 40 45 67.5 0.7 1.2
37 50 55 82.5 0.5 0.85
45 60 80 120 0.4 0.7
55 75 80 120 0.4 0.7
75 100 100 150 0.3 0.45
B.6.2 AC Output Reactor Recommended Value
230V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance 5% impedance
0.75
1 8 12 3
5
1.5
2 8 12 1.5
3
2.2
3 12 18 1.25
2.5
3.7
5 18 27 0.8
1.5
5.5
7.5 25 37.5 0.5
1.2
7.5
10 35 52.5 0.4
0.8
11
15 55 82.5 0.25
0.5
15
20 80 120 0.2
0.4
18.5
25 80 120 0.2
0.4
22
30 100 150 0.15
0.3
30
40 130 195 0.1
0.2
37
50 160 240 0.075
0.15
Commentaires sur ces manuels