AMX Distributed Audio Controllers Delta Series Spécifications Page 140

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 239
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 139
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-83
09 - 02 Transmission Fault Treatment
Factory Setting: 03
Settings 00 Warn and keep operating
01 Warn and RAMP to stop
02 Warn and COAST to stop
03 No warning and keep operating
This parameter is set to how to react if transmission errors occur.
See list of error messages below (see section 3.6.)
09 - 03 Time-out Detection Unit: 0.1
Settings 0.0 ~ 60.0 sec Factory Setting: 0.0
0.0 Disable
If Pr.09-03 is not equal to 0.0, Pr.09-02=00~02, and there is no communication on the bus
during the Time Out detection period (set by Pr.09-03), “cE10” will be shown on the keypad.
09 - 04 Communication Protocol
Factory Setting: 00
Settings 00 Modbus ASCII mode, protocol <7,N,2>
01 Modbus ASCII mode, protocol <7,E,1>
02 Modbus ASCII mode, protocol <7,O,1>
03 Modbus RTU mode, protocol <8,N,2>
04 Modbus RTU mode, protocol <8,E,1>
05 Modbus RTU mode, protocol <8,O,1>
1. Control by PC or PLC
A VFD-B can be set up to communicate on Modbus networks using one of the following modes:
ASCII (American Standard Code for Information Interchange) or RTU (Remote Terminal Unit).
Users can select the desired mode along with the serial port communication protocol in Pr.09-04.
Code Description:
ASCII mode:
Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data:
64 Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code 30H 31H 32H 33H 34H 35H 36H 37H
Vue de la page 139
1 2 ... 135 136 137 138 139 140 141 142 143 144 145 ... 238 239

Commentaires sur ces manuels

Pas de commentaire